30-2500kVA/10kV Low-Loss Oil Immersed Transformer
2025-04-13 18:31  Visit:295
Price:Unfilled
Brand:S11
Send inquiry
Product Overview
 

 

The S11 oil immersed hermetically sealed type transformer, as an upgraded version of the S9 series, achieves an average 20% reduction in no-load losses and 15% lower load losses compared to the S9. Utilizing high-permeability silicon steel sheets and a foil winding structure, it enhances short-circuit resistance by 30% and reduces operational noise by 5dB relative to the S9. This design innovation ensures compliance with stricter energy efficiency standards while delivering superior performance in demanding power distribution applications.

 

 

 

Type And Meaning
 

 

 

 

 

Application Scope
 

 

  • Normal use Environment:Elevation less than 1000m;Temperature Range: -25℃~+40℃
  • Especial Environment :Elevation more than 1000m;Temperature Range: -45℃~+40℃
  • Installation Site: Nothing corrodent air, noting obvious dirty mark

 

 

 

Executive Standards
 

 

GB1094.1~2-1996

GB1094.4-2005

GB1094.3, 5-2003

GB/T6451-2008

 

 

 

Product Features
 

 

1. Comparison of the series transformer and S9 transformer, no-Load Loss is reduced by an average of about 30%.

2. We adopt structure of canister type or helix type at capacity rang 630kv to 2000kv for Low voltage coil; they are high machine intensity, balance distribution, good capacity of anti-short circuit.

3. We add a orientation structure, which make it don' t occur to move in the transport; accordingly add a nut in the product which makes sure the part don't fall down in function.

4. Spurting the varnish on the product after getting rig of the rust and oil mark, which make the product can used in special environment.

5. The ripple gasoline rank instead of oil cabinet, sealing the cabinet cover with cabinet edge, which extends the oil service life.

 

 

 

Main Technical Parameters
 

 

Rated

Capacity

(kVA)

Voltage

Vector Group

No-Load

Loss

(W)

On-Load

Loss

(W)

Short

cirait-z

(%)

No-Load

Cur

(%)

Weight(kg)

Size(mm)

Distance

(mm)

V

(kV)

Chng

(%)

V

(kV)

Wain w.t

Oil w.t

Ttl w.t

L·W·H

30

6

6.3

10

10.5

11

±5%

Or

±2×2.5

0.4

Yyn0

Or

Dyn11

100

600/630

4.0

2.1

200

65

325

700×555×870

400×400

50

130

870/910

2.0

215

100

420

820×660×935

400×400

63

150

1040/1090

1.9

260

110

460

850×660×950

400×400

80

180

1250/1310

1.8

310

120

540

870×665×970

400×450

100

200

1500/1580

1.6

350

145

620

880×670×1010

400×450

125

240

1800/1890

1.5

415

170

710

930×690×1040

450×550

160

280

2200/2310

1.4

485

180

830

865×765×1050

550×550

200

340

2600/2730

1.3

540

185

066

1200×770×1070

550×550

250

400

3050/3200

1.2

640

190

1130

1270×830×1120

550×550

315

480

3650/3830

1.1

750

230

1330

1420×960×1190

550×550

400

570

4300/4520

1.0

900

260

1560

1420×960×1220

660×660

500

680

5150/5410

1.0

1040

300

1800

1500×1010×1275

660×660

630

810

6200

4.5

0.9

1250

380

2125

1650×1140×1350

660×660

800

980

7500

0.8

1470

440

2490

1750×1200×1510

820×820

1000

1150

10300

0.7

1720

500

2900

1780×1260×1550

820×820

1250

1360

12000

0.6

1860

580

3580

1860×1300×1610

820×820

1600

1640

14500

0.6

2280

730

4070

1940×1360×1660

820×820

2000

2020

17820

Please contact us for detailed data

2500

2380

20700

 

Note:

1. Load loss in the table below the diagonal values for Dyn11 connection group of products.

2. Technical parameters of 10kV distribution transformer for large capacity, size and weight data, please contact us.

3. Can provide various voltage transformer, short circuit impedance, coupling mode according to the user demand.

4. Table weight and size data for reference only, are subject to change without notice.

 

 

 

FAQ
 

 

Q: How long is the delivery time?

A: Normal within 10 days. It depends on detail items and quantity.Please contact us for details.

Q: How to get product quotation?

A: You can contact us anytime through the contact information on the website. You will receive our response within 24 hours.

Q: What after-sales services can I enjoy?

A: The transformer comes with a one-year warranty. Long-term online technical support is provided, along with customer training, and regular updates to maintenance manuals and technical guides.

Q: How long is the average lifespan of a transformer?

A: The lifespan ranges from 20 to 40 years, influenced by factors such as maintenance level, operating environment, and load conditions.

Q: How to determine the parameters of the transformer?

A: We can usually find the parameters in transformer nameplates, drawings, outline drawings, and technical tables.

Q: Do you have oil-immersed transformers and dry-type transformers in stock?

A: No, as transformers require customized parameters based on demand, we usually need to design them after receiving an order.

 

 

 

http://www.lvma-transformer.com/

Message

TO: zjlmjck

E-mail:

Content:

Contact information
Comment
0